Energia, controllo e segnalamento - Low smoke zero halogen

HSLCH-OB/-JB/-OZ/-JZ B2ca
Marcatura 
<meters> CE 0987 SPECIALCAVI BALDASSARI HSLCH <formation> IEC 60332-3-24 <lot> <year> B2CA-S1A,D0,A1
Caratteristiche costruttive
Anima 

Flexible bare copper conductor, class 5

Isolamento 

LSZH thermoplastic compound, TI6 type

Cordatura 

Cores twisted/stranded in concentric layers

Fasciatura e protezione 

Polyester tape

Schermatura 

Tinned copper braid

Guaina esterna 

LSZH thermoplastic compound, TM7 type

Colori 

Cores identifcation:
HD 308 S2 (-OB/-JB)
Black numbered w/ (-JZ) or w/o Green/Yellow (-OZ)
Outer sheath colour:
Grey (based on RAL 7001)

Caratteristiche elettriche
Tensione di esercizio anime 

• 300/500V section ≤ 2.5 mm2 • 450/750V section = 4.00 and 6.00 mm2 • 0.6/1kV section ≥ 10.00 mm2

Tensione di esercizio guaina esterna 
• 300/500V section ≤ 2.5 mm2 • 450/750V section = 4.00 and 6.00 mm2 • 0.6/1kV section ≥ 10.00 mm2
Tensione di prova 

• 2000V section ≤ 2.5 mm2 • 2500V section = 4.00 and 6.00 mm2 • 4000V section ≥ 10.00 mm2

Certificazioni
Riferimento normativo 

IEC 60228
IEC 60332-3-24 Cat.C

Classe di reazione al fuoco 
EN 50575:2016 B2ca - s1a, d0, a1
Temperature
Temperatura minima di esercizio 

• Fixed laying -40°C • Occasional mobile laying w/o stress -5°C

Temperatura massima di esercizio 

• Fixed laying +70°C • Occasional mobile laying w/o stress +70°C

Temperatura massima cortocircuito 
+160°C
Su richiesta 

• Customized cores identification/outer sheath colour

Condizioni di posa
Temperatura minima di posa 0°C
Raggio minimo di posa: vedi scheda tecnica
Max sforzo di tiro: vedi scheda tecnica
Posa fissa
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In tubo o canalina in aria
In buried trough (0.6/1kV)
Buried with protection (0.6/1kV)
In buried duct (0.6/1kV)
Directly buried (0.6/1kV)
Il cavo stoccato/posato in esterno deve essere protetto dai raggi UV
Applicazioni 

Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.

Multi-core LSZH cable for power transport and for control, signaling, command and measurement systems with scaled-down outer dimensions and excellent flexibility. Used in industry for machine cabling, transport systems, production lines and in the connection of air conditioning and heating systems, industrial equipment and power stations.
Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress. The screening helps to protect against electromagnetic interference.

If stored outdoors, the cable must be protected from UV rays.
300/500V and 450/750V: Underground laying is not permitted even if protected.
0.6/1kV: Direct or indirect underground laying is permitted.