Fire resistant and LSZH

FTE29OHM16 PH120
Marcatura 
<metrica progressiva> CE SPECIALCAVI BALDASSARI FTE29OHM16 PH120 100/100V <formazione> EN 50200 CEI 20-105 CEI 36762 C-4 (U0=400V) <lotto> <anno> CCA-S1B,D1,A1
Manufacturing characteristics
Core 

Flexible bare copper, class 5

Fire resitant barrier 

Mica tape

Insulation 

LSZH cross-linked compound, E29 type

Stranding 

Cores twisted/stranded in concentric layers

Wrapping and protection 

Overall polyester tape

Screen 

Overall aluminium/polyester tape with flexible bare copper drain-wire

Outer sheath 

LSZH thermoplastic compound, M16 type

Colours 

Cores identification:
2 cores = Red + Black
4 cores = Red + Black + White + Blue
Outer sheath colour:
Red (based on RAL 3000)
 

Electrical characteristics
Tensione di esercizio anime 

100/100V

Tensione di esercizio guaina esterna 
100/100V C-4 (U0=400V)
Tensione di prova 

2000V

Certifications
Standard 

CEI 20-29 IEC 60228
CEI 20-11 
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI 20-105, V1, V2
CEI 20-36/4-0 EN 50200 (Durata test 120 min. PH120)
CEI UNEL 36762
UNI 9795:2021

Reaction to Fire Class 
EN 50575:2016 Cca - s1b,d1,a1
Temperature
Temperatura minima di esercizio 

-40°C

Temperatura massima di esercizio 

+90°C

Temperatura massima cortocircuito 
+250°C
On request 
  • Customized cores identification/outer sheath colours
  • Reinforced outer sheath for underground laying in duct
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d14
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In duct or cable tray
The cable stored outside must be protected from UV rays
Applications 

Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.

LSZH shielded cable for signalling and command, fire-resistant (PH120) according to CEI 20-105, V1, V2 and UNI 9795:2021.

It can be used for connecting fixed automatic detection and manual fire alarm signalling systems, whether or not connected to fire extinguishing systems (both active and passive types), planned to be installed in buildings, regardless of their intended use.

Suitable for links between fire-fighting systems and actuators (e.g. electric locks, smoke and heat natural evacuators, electromagnets for releasing fire doors, etc.) with 12V and 24V AC operating voltage.

This cable, if it’s used to supply power to category 0 systems (nominal voltage less than or equal to 50V AC, or 120V noninverted DC), it can also be installed in coexistence with 450/750V or 0.6/1kV power cables that supply 230/400V nominal voltage loads.

If stored outdoors, the cable must be protected from UV rays. Underground laying is not permitted, even if protected.