LiYCY-TP-DIN Dca
Trasmissione dati e strumentazione
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI LIYCY-TP <formation> IEC 60332-3-24 <lot> <year> DCA-S3,D0,A3
Caratteristiche costruttive
Anima
Flexible bare copper conductor, class 5
Isolamento
PVC compound, flame retardant
Cordatura
Cores twisted in pairs
Pairs stranded in concentric layers
Fasciatura e protezione
Overall polyester tape
Schermatura
Overall tinned copper braid
Guaina esterna
PVC compound, flame retardant
Colori
Cores identification:
DIN 47100
Outer sheath colour:
Grey (based on RAL 7001)
Caratteristiche elettriche
Tensione di esercizio anime
- 300/500V section ≤ 0.75 mm²
- 450/750V section ≥ 1.00 mm²
Tensione di esercizio guaina esterna
450/750V
Tensione di prova
- 2000V section ≤ 0.75 mm²
- 2500V section ≥ 1.00 mm²
Certificazioni
Riferimento normativo
IEC 60228
IEC 60332-3-24 Cat.C
Classe di reazione al fuoco
EN 50575:2016 Dca - s3, d0, a3
Temperature
Temperatura minima di esercizio
- Fixed laying -25°C
- Occasional mobile laying w/o stress -5°C
Temperatura massima di esercizio
- Fixed laying +70°C
- Occasional mobile laying w/o stress +70°C
Temperatura massima cortocircuito
+160°C
Su richiesta
• Customized cores identification/outer sheath colour
Condizioni di posa
Temperatura minima di posa 0°C
Raggio minimo di posa: vedi scheda tecnica
Max sforzo di tiro: vedi scheda tecnica
Posa fissa
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In tubo o canalina in aria
Applicazioni
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Multi-pair cables with overall screening for data transmission in electronics and computers, for signaling, measurement, command and control systems, and more generally, where there is a need for efficient protection from external electromagnetic disturbance and compact size.
Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.
Underground laying is not permitted even if protected.